Concrete
equipment shelters are engineered and built for ultimate strength,
durability and protection; providing substantial vandal and bullet resistance
-
plus extremely low maintenance. With 4-inch thick,
steel reinforced poured concrete walls, your shelter will far exceed the
UL-752 rating for all firearm classes up to and including 30:06, high power
rifle at point-blank range.
Each concrete shelter is hand built in
a climate controlled environment, keeping materials dry and
construction on schedule. Your shelter will move down an assembly line where skilled workers meticulously complete
tasks they have perfected through
ongoing
training, repetition and strict quality control. In addition, periodic inspections
are performed by State or third-party building inspectors. The result brings you an equipment shelter
well capable of protecting your valuable contents for many decades.
ADVANTAGES and APPLICATIONS for CONCRETE
SHELTERS:
-
Ultimate protection for desolate and seasonally
inaccessible sites.
-
Locations having an elevated risk of
theft or
vandalism.
-
In or around hunting
areas or preserves; resists
stray bullets.
-
Regions with risk of heavy snow &
ice, tornados,
hurricanes, etc.
-
Hazardous material
storage building. Add optional explosion-proof lighting, wiring,
switches and ventilation.
-
Shear Wall design resists seismic
stress.
  
  
SEE INTERIORS
  
YOU MAY NOT NEED
A FOUNDATION!
The 6.75-inch steel-reinforced poured concrete floor may eliminate,
depending on location, the need for a foundation. A prepared base of gravel, stone or sand
may be sufficient to permanently set your SERIES-I. When placed under or adjacent
to towers, the concrete roof provides excellent protection from
falling ice.
Concrete shelters
are available in a variety of exterior treatments, from earth-tone washed aggregate to
any desired siding texture or material
- basically, we will deliver whatever architectural look you need to satisfy local
zoning and code officials. If the desired finish is real brick or
stone, Miller Construction Services (MCS)
will assure your exterior is completed on-site following delivery!
STANDARD SPECIFICATIONS:
(Minimums)
Floor Loading: 200 PSF
- 6.75-inch reinforced concrete w/
step joint design
Roof Loading: 150 PSF
- 5-inch reinforced concrete at
ridge, 4-inch at eave
Wind Loading: 150 MPH
- 4-inch steel-reinforced concrete
walls
CONSTRUCTION NOTES:
-
Conforms to ACI-318 building code
requirements for reinforced concrete.
-
Concrete is lightweight (112
lbs./cu. ft.), with a minimum compressive strength of 5000 PSI at 28
days.
-
Steel reinforcing bars are domestic,
new billet steel conforming to ASTM A-615 grade 60 specifications.
-
Concrete coverage over all steel
conforms to ACI-318 building code.
-
All rebar is tied or welded 100% at
perimeter and 50% elsewhere.
MATERIALS:
-
1.5-inch foil-faced rigid board R-11
insulation on walls & roof.
-
.4375-inch white embossed FRP
laminated interior walls & ceiling.
-
.125 x 12 x 12 inch commercial-grade
flooring tile.
-
16 gauge doors w/14 gauge frame,
galvanized steel primed & painted.
-
4-inch high cove base molding.
WALL and ROOF SEALANT APPLICATIONS:
-
Urethane sealant inside and outside
joist.
-
Exterior wall surface sprayed w/ 2
coats of silicone penetrating sealant.
-
Roof, trawled and broom finish w/ elastomeric coating applied to in 3 parts.
REBAR SCHEDULE:
-
Wall Panel #4 short and long axis
-
Roof Panel #6 short axis and #4 long
axis
-
Floor Panel #6 short axis and #4 long
axis.
 TURNKEY
OPTION:
Each MILLER shelter is custom built with specified electrical
service, generator, alarms, HVAC, UPS, racks, etc. If you
elect to ship your electronics - to our secure facility - our highly-trained technicians will
mount all radio equipment and deliver your shelter
ready for testing!
RETURN TO SHELTER CATEGORIES